Oregon Bulletin
Rule
Caption: Providing flexibility to approve
loans to school districts as part of the Governors School Initiative.
Adm.
Order No.: DOE 4-2011(Temp)
Filed with Sec. of
State: 6-20-2011
Certified to be
Effective: 6-20-11 thru 12-17-11
Notice Publication
Date:
Rules Adopted: 330-105-0017
Subject: The rule allows the department to approve specific
loans as part of the Governors School Initiative pilot program without prior
review of the Committee, if these loans meet standards set in rule. Standards
relate to the size, purpose and security on the loan, and the type of borrower.
Rules Coordinator: Kathy Stuttaford—(503) 373-2127
330-105-0017
Governors School Initiative Pilot
(1) In addition to the allowances provided under
330-105-0015 (2) the department may, without prior review of the Committee,
approve loans that are:
(a) Part of the Governor’s School Initiative pilot
program;
(b) Under $5 million;
(c) For measures in K–12 facilities;
(d) Issued to school districts; and
(e) To be secured for their full loan amount by a
resolution by the governing body of the borrower.
(2) Any approvals made by the department under the
provisions of this section shall be presented at the next scheduled meeting of
the Committee.
Stat. Auth.: ORS 470.080
Stats. Implemented: ORS 470.080
Hist.: DOE 4-2011(Temp), f. &
cert. ef. 6-20-11 thru 12-17-11
Rule
Caption: Modifies program requirements to
align with industry standards and provide flexibility.
Adm.
Order No.: DOE 5-2011
Filed with Sec. of
State: 6-27-2011
Certified to be
Effective: 6-27-11
Notice Publication
Date: 3-1-2011
Rules Adopted: 330-130-0025
Rules Amended: 330-130-0010, 330-130-0020, 330-130-0030,
330-130-0040, 330-130-0050, 330-130-0055, 330-130-0060, 330-130-0070,
330-130-0080, 330-130-0090, 330-130-0100
Subject: The rule amendments provide additional clarity and
flexibility in the State Energy Efficient Design (SEED) program. They include
new definitions for “Highly efficient facility” and Leadership in Energy
Efficient Design (LEED) certification. The process for SEED rules is
streamlined to allow LEED certification, Oregon Reach Code or other
substantially equivalent standard exemption from duplicative SEED processes and
establishes criteria which must be met to demonstrate energy
efficiency standards have been achieved.
Rules Coordinator: Kathy Stuttaford—(503) 373-2127
330-130-0010
Purpose
These rules prescribe procedures to promote the design,
construction and renovation of highly energy efficient buildings owned and
operated by state agencies by:
(1) Minimizing energy use by incorporating the Optimum
Energy Conservation Measures Package as defined in these rules into the final
building design; and
(2) Reducing agency energy use by 20 percent in
existing buildings by the year 2015 compared to the year 2000.
Stat. Auth.: ORS 276.900 -
276.915, Ch. 26, OL 2008 HB 3612
Stats. Implemented: ORS 469
Hist.: DOE 1-1990, f. & cert.
ef. 4-2-90; DOE 1-1998, f. & cert. ef. 3-26-98; DOE 4-2001, f. 11-5-01, cert. ef. 11-15-01; DOE 5-2008, f. 7-29-08, cert. ef. 8-1-08; DOE 5-2011, f. & cert. ef. 6-27-11
330-130-0020
Definitions
(1) “Agency” means the authorized state agency, board,
commission, department or division which has the authority to enter contracts,
finance the construction, purchase, renovation, or leasing of buildings or
other structures for use by the State of Oregon.
(2) “Agency contact” means a lead person appointed by
the agency who is responsible to coordinate all State Energy Efficient Design
related business with the Oregon Department of Energy, such as project
notifications, interagency agreements, invoice and payment, project coordination,
guideline updates and advisory recommendations.
(3) “Baseline building” means the basic building
conceived by the agency and the design team. The baseline building incorporates
the standard design features of typical buildings of the same usage and meets
the prescriptive or performance requirements of the Oregon Energy Efficiency
Specialty Code according to criteria established in the State Energy Efficient
Design Program Guidelines.
(4) “Benefit-to-Cost Ratio (BCR)” means the present
value of Energy Conservation Measure benefits divided by the present value of
incremental Energy Conservation Measure costs.
(a) The Energy Conservation Measure benefit is the
difference between the present values of the operating cost of the baseline
building and the operating cost of the baseline building with the Energy
Conservation Measure added.
(b) The incremental Energy Conservation Measure cost is
the difference between the present values of the capital cost of the baseline
building and the capital cost of the baseline building with the Energy
Conservation Measure added.
(5) “Biennial report” means the report summarizing the
progress toward achieving the goals of ORS 276.900 through ORS 276.915.
(6) Building Class:
(a) “Class 1 Building” means all:
(A) New buildings, additions, or renovations of 10,000
or more square feet of heated or cooled floor area; and
(B) Building additions that increase the size of an
existing building to 10,000 or more square feet of heated or cooled floor area
and renovations to buildings of 10,000 or more square feet of heated or cooled
floor area, which significantly affect:
(i) The existing mechanical or control system; or
(ii) At least two of the following energy systems:
interior lighting, building envelope, domestic hot water, or special equipment.
(iii) Only those systems identified in (i) and (ii)
that are significantly affected are subject to procedures outlined in
330-130-0040.
(b) “Class 2 Building” means all new buildings or
renovations of less than 10,000 square feet of heated or cooled floor area
except for new buildings, structures, or facilities of any size
which have no energy using systems.
(7) “Building model” means a computer model, which
calculates annual building energy use. The Oregon Department of Energy shall
approve hourly building models, simplified hourly building models and the
approach to modeling Energy Conservation Measure energy savings above the
baseline building as established in the State Energy Efficient Design Program
Guidelines. The building model for all Class 1 Buildings must be an hourly
building model, except for certain Class 1 buildings as approved by the Oregon
Department of Energy where simplified hourly building modeling or prescriptive
packages established in the State Energy Efficient Design Program Guidelines
may be used.
(8) “Capital construction cost” means the cost of
current and future building investments including construction, design,
administration, major replacement, and salvage values. Costs of compliance with
these rules may also be included.
(9) “Commissioning agent” is an individual or firm that
has demonstrated experience commissioning Heating, Ventilating, and Air
Conditioning (HVAC) mechanical systems and HVAC control systems, commercial and
industrial mechanical technologies, lighting controls, and testing and
balancing of air and water systems.
(10) “Contracting agency” means the agency entering
into a contract for facility construction or renovation.
(11) “Department” means the Oregon Department of
Energy.
(12) “Design team” means the architect(s), engineer(s),
and other professionals who are responsible for the design of the new building
or renovation.
(13) “Director” means the director of the department.
(14) “Energy Use Index (EUI)” is a calculated index
that describes a building’s energy use in relation to a metric, generally
square feet, such as kBtu/ft2 –yr or kWh/ft2 –yr.
(15) “Energy analysis report” means a report prepared
by an energy analyst, under the direction of a professional engineer or
licensed architect, recommending an Optimum Energy Conservation Measure Package
for a Class 1 building. The report must include:
(a) Department State Energy Efficient Design forms;
(b) A summary of recommendations;
(c) A baseline building description;
(d) Energy Conservation Measure descriptions with
analysis results;
(e) Energy Conservation Measure savings calculations;
and
(f) Energy Conservation Measure cost estimates.
(16) “Energy analyst” means the individual who prepares
the building energy analysis and the energy analysis report under the direction
of a professional engineer or licensed architect who reports to the project
architect or agency.
(17) “Energy auditor” is an individual or firm that has
demonstrated experience performing comprehensive analysis of a building’s
energy using systems, and performs benefit to cost analysis of energy
efficiency measures.
(18) “Energy Conservation Measure (ECM)” means a
measure designed to reduce energy use, including alternative energy systems which replace conventional fuels with renewable
resources. ECMs must not conflict with applicable codes and other professional
standards.
(19) “ECM Package” means two or more ECMs combined for
analysis.
(20) “Energy Service Company (ESCO)” means a company,
firm or other legal person with the demonstrated technical, operational,
financial and managerial capabilities to design, install, construct,
commission, manage, measure and verify, and otherwise implement ECMs and other
work in building systems or building components that are directly related to
the ECMs in existing buildings and structures.
(21) “Energy Services Performance Contract (ESPC)”
means a public improvement contract between a contracting agency and a
qualified energy service company for the identification, evaluation,
recommendation, design, and construction of ECMs, including a Design Build Contract, that guarantees the energy savings performance.
(22) “Energy systems performance verification plan”
means a plan that outlines how the building’s energy systems are to be tested
during the construction phase and how the building’s performance is to be
verified with long-term monitoring during occupancy.
(23) “Highly efficient facility” means a facility that
is designed, built and operated according to these State Energy Efficient
Design rules, that makes use of renewable energy resources where practical,
that incorporates all cost-effective energy efficiency measures, and exceeds
the requirements of the Oregon Energy Efficiency Specialty Code.
(24) “Leadership in Energy Efficient Design (LEED)” is
an internationally recognized green building certification system, providing
third-party verification that a building or community was designed and built
using strategies intended to improve performance in metrics such as energy
savings, water efficiency, greenhouse gas emissions reduction, improved indoor
environmental quality, and stewardship of resources and sensitivity to their
impacts.
(25) “Measurement and verification (M&V)” means, as
used in ESPC Procurement, the examination of installed ECMs using the
International Performance Measurement and Verification Protocol or process, to
monitor and verify the operation of energy using systems pre-installation and
post-installation.
(26) “Net Present Value Savings (NPVS)” means the
difference between the present values of the capital and operating costs of the
baseline building and the capital and operating costs of the baseline building
with the ECM added.
(27) “OEESC” means the Oregon Energy Efficiency
Specialty Code adopted pursuant to OAR 918-460-0500.
(28) “Operating cost” means the costs for energy, fuel,
annual and periodic maintenance, supplies, consumables, and other operating
items associated with ECMs, such as water and sewer, during the life of the
building.
(29) “Optimum ECM Package” means the ECM package which
incorporates all reasonable cost-effective ECMs and which meets the following
conditions:
(a) Each ECM included in the package has a BCR greater
than 1.0 when modeled independently.
(b) The ECM package has a BCR greater than 1.0.
(c) The ECM Package has the highest NPVS of the
analyzed ECM packages.
(30) “Oregon Reach Code” is a set of construction
standards adopted under ORS 455.490 to 455.595.
(31) “Present value” means the
value of a financial cost or benefit, discounted to current dollars using
discounting factors and methods approved by the department.
(32) “Renewable energy resource” includes, but is not
limited to, on-site generation of energy for use in the building from the
following sources:
(a) Straw, forest slash, wood waste or other wastes
from farm or forest land, nonpetroleum plant or animal based biomass, ocean
wave energy, solar energy, wind power, water power or geothermal energy; or
(b) A hydroelectric generating facility that obtains
all applicable permits and complies with all state and federal statutory
requirements for the protection of fish and wildlife and:
(A) That does not exceed 10 megawatts of installed
capacity; or
(B) Qualifies as a research, development or demonstration
facility.
(c) The purchase of renewable energy certificates does
not qualify as a renewable energy resource.
(33) “SEED” means State Energy Efficient Design Program
as defined in ORS 276.900 through ORS 276.915 under the heading State Agency
Facility Energy Design.
(34) “SEED Program Guidelines” are guidelines developed
by the department with assistance from an advisory committee that consists of
representatives from interested agencies, design professionals, consulting
engineers and utilities.
(35) “Simple payback” means the estimated ECM cost
divided by the estimated first year ECM energy, operating, and maintenance
savings.
[Publications: Publications
referenced are available from the agency.]
Stat. Auth.: ORS 276.900 - 276.915
Stats. Implemented: ORS 469
Hist.: DOE 1-1990, f. & cert.
ef. 4-2-90; DOE 1-1998, f. & cert. ef. 3-26-98; DOE 4-2001, f. 11-5-01, cert. ef. 11-15-01; DOE 5-2008, f. 7-29-08, cert. ef. 8-1-08; DOE 5-2011, f. & cert. ef. 6-27-11
330-130-0025
Alternate Compliance Paths
(1) If an agency intends to seek LEED certification, or
build to the Oregon Reach Code or build to some other substantially equivalent
national standard for a building project the following shall apply:
(a) The agency must notify the department in writing of
their intention to seek LEED certification, or build to the Oregon Reach Code
or build to a substantially equivalent national standard. When an agency wishes
to build to a substantially equivalent national standard, the department must
agree and certify in writing that the standard is “substantially equivalent”
before the agency can proceed.
(b) The agency must comply with energy consumption
analysis and review requirements of the SEED Program Guidelines;
(c) The agency must provide documentation to the department
throughout the design, construction and post-occupancy phases to verify that
all SEED requirements are met as specified in the SEED Program Guidelines; and
(d) Agencies following the LEED path must achieve a
minimum of 12 points in the Energy and Atmosphere Credit Number 1 Category
(Optimize Energy Performance).
(2) A donated building is exempt from the SEED rules
until the agency assumes the title to the building.
Stat. Auth.: ORS 276.900 - 276.915
Stats. Implemented: ORS 276.900 -
276.915
Hist.: DOE 5-2011, f. & cert.
ef. 6-27-11
330-130-0030
Notification
When the building class has been determined during the
pre-design or programming phase of a building project, the following procedures
shall be followed:
(1) Class 1 Buildings. Before the design team is
selected, the agency and the department may enter into an interagency agreement which outlines the procedures as shown in OAR
330-130-0040, the hourly rates to be charged by the department and the related
statement of work. The agency contact shall coordinate with the department to
set-up the initial meeting early in the pre-design or programming phase of a
building project. The interagency agreement may include expanded services under
OAR 330-130-0040(9).
(2) Class 2 Buildings. The agency shall contact the
department for consultation and request a list of recommended ECMs and services
applicable to the building.
Stat. Auth.: ORS 276.900 - 276.915
Stats. Implemented: ORS 469
Hist.: DOE 1-1990, f. & cert.
ef. 4-2-90; DOE 1-1998, f. & cert. ef. 3-26-98; DOE 4-2001, f. 11-5-01, cert. ef. 11-15-01; DOE 1-2003, f. & cert. ef. 1-10-03;
DOE 5-2008, f. 7-29-08, cert. ef. 8-1-08; DOE 5-2011,
f. & cert. ef. 6-27-11
330-130-0040
Procedures for Class 1 Buildings
(1) The
SEED process follows typical design process steps as the organizing principle.
If the agency is accustomed to using different phases or terminology, or if the
project does not fit the suggested steps, an alternative plan may be developed
between the department and the agency.
(2) Meetings in this section of these rules may be
eliminated or combined with other meetings as deemed appropriate by the
department.
(3) Pre-Design or Programming Phase. The purpose of the
SEED process is to ensure early involvement so energy efficiency is an integral
part of the building design.
(a) Initial Meeting. Early in the pre-design or
programming phase, the agency and the department shall meet to:
(A) Discuss the scope of the project;
(B) Define the role of the department including, but
not limited to, the level of involvement, decision authority on behalf of the
owner, and relationship with contractors. The department shall be notified of
all meetings where significant review of or final decisions about energy
systems are anticipated.
(C) Develop the request for proposal (RFP) and
contract. The RFP and the contract’s statement of work must include a reference
to building a “highly efficient facility” as defined in these rules and to the
SEED process. The department may develop language the agency may use to include
energy efficient design in the request for proposals and the contract for
architectural and engineering services. Upon request, the department will
review or comment on the RFP, contract or energy qualifications of proposals as
an expanded service under section (9).
(D) The agency must hire an energy analyst as described
in OAR 330-130-0090(2)(a).
(b) Schematic Design Phase:
(A) Energy Planning Session. Early in the Schematic
Design Phase, the agency, design team, department and energy analyst shall meet
to further define the items in the list below:
(i) Project design;
(ii) Construction schedule;
(iii) Energy goals of the project
(iv) Design criteria;
(v) Integrated energy design approach;
(vi) Energy systems performance verification plan; and
(vii) Modeling approach.
(B) Preliminary Investigation. Working with the agency
and the design team, the energy analyst must prepare a comprehensive list of
ECMs to capture significant opportunities for building energy savings. Two
weeks before the scoping process (under section (2)(c)), the agency must
deliver to the department the following items:
(i) Description of the baseline building and its
energy-using systems;
(ii) List of proposed ECMs;
(iii) Approach and tools for modeling;
(iv) Initial plans;
(v) Design intent;
(vi) Description of operating criteria; and
(vii) Results of preliminary modeling effort, if any.
(c) Scoping Process. The department, the agency, the
design team, and the energy analyst shall select the ECMs for analysis. If
needed, further refinement of the modeling effort may be discussed and decided
upon.
(4) Design Development Phase:
(a) Baseline and individual ECM analysis. The energy
analyst shall use the building model for baseline building analysis and
individual ECM analysis. The energy analyst may use fully documented manual
calculations for simple, non-interactive ECMs and may eliminate potential ECMs
with preliminary estimates of costs and savings if the simple payback is
greater than the equipment life.
(b) Metering Plan. The agency, in consultation with the
energy analyst, the design team and the department, must specify what types of
utility meters are to be installed and what system is to be used to monitor the
building’s energy use. Where practical, sub-metering shall be provided on major
energy-using equipment or systems. This Metering Plan must be incorporated in
the energy systems performance verification plan.
(c) Interim Submittal and Review. Two weeks before the
ECM Review Meeting, the agency must submit to the department the preliminary
energy analysis report. The department must review the preliminary energy
analysis report and provide its written or verbal comments and recommendations
to the agency prior to the ECM review meeting. The following items must be
submitted as part of the preliminary energy analysis report:
(A) Narrative describing the baseline building and the
proposed ECMs;
(B) Tables showing energy use for the baseline building
and the building with proposed ECMs;
(C) Baseline building model input and output;
(D) List of eliminated ECMs and calculations;
(E) Analysis results for individual ECMs; and
(F) Metering plan.
(d) ECM Review Meeting. The department, the agency, the
design team, and the energy analyst shall meet to review and agree on the
results in the preliminary energy analysis report.
(5) Construction Documents Phase:
(a) Implementation of Cost-Effective Measures. The
agency must incorporate the Optimum ECM Package into the final building design.
(b) Submittal of Construction Documents. The agency
shall provide the department with construction documents in sufficient detail
to verify that the Optimum ECM Package will be included in the final
construction documents and specifications no later than at 90 percent design
completion. This submittal must also include the preliminary energy systems
performance verification plan.
(c) The department shall review this submittal and
forward its written findings and recommendations to the agency within 10
working days after receiving the documents, if practicable.
(6) Construction Phase:
(a) Contractor Submittals and Substitutions. The design
firm shall ensure that contractor equipment submittals, requests for
substitutions and change orders adhere to the ECM design intent. The design
firm must send any substitutions or submittals that differ from the ECM design
intent to the department for review.
(b) Final Report Submittal. The agency shall deliver
the final energy analysis report containing the Optimum ECM Package and
projected energy use to the department for review.
(c) Delivery of the department findings. The department
shall review the report and forward its written findings and recommendations to
the agency within 10 working days after receiving the report, if practicable.
(d) Site Inspections. To verify that ECMs are installed
correctly and operating efficiently, the department or its representative may
make walk-through site inspections during the installation of ECMs.
(e) Performance verification. The energy systems
performance verification plan must be carried out and a copy of the test
reports must be submitted to the department.
(f) Training. It is recommended that instruction on the
design intent and operation of the building as a system be offered to the owners and operators of the new facility. This may be part of
the energy systems performance verification plan. The training should parallel
the operations manual prepared for the owner.
(7) Occupancy Phase:
(a) Monitoring. At completion of functional testing
(approximately two months after occupancy begins), a meeting may be held
between the agency, building operator, general contractor, commissioning agent,
and energy analyst to review building energy use. Actual building operation
will be compared with assumptions made in the final design phase energy
analysis. If significant differences in schedules, equipment, operation, etc.
exist, a calibrated energy model must be submitted at the discretion of the
department (if actual energy use is outside five percent (+/-) of predicted
energy use). During the first 18 months into occupancy, energy use by the
building systems must be monitored and compared with the modeling results. If
significant differences between the actual energy use and the model predictions
result, the agency must investigate to find the cause, so that:
(A) An adjustment can be made to the operation of the
building; or
(B) An explanation for the difference can be found that
is acceptable to the agency and the department. The agency must send its
finding to the department.
(b) Non-compliance. If, after monitoring the building
for 18 months, the building’s performance does not meet the projected energy
use because of reasons reported under (7)(a), the agency shall submit an energy
conservation plan to the department within 90 days after reporting the
non-compliance. This plan will outline the modifications to be made until
monitoring shows that the building meets the projected energy use, or all
reasonable attempts to reduce the energy use have been made. A report of these
remedial actions must be submitted to the department.
(c) SEED Award. The department shall give the SEED
Award to the agency if the building complies with these SEED rules, is a
“highly efficient facility,” and meets the criteria for the SEED award as
determined in the SEED Program Guidelines.
(8) Waiver. The director of the department may waive
part of these rules when an agency cannot comply due to extenuating
circumstances such as a conflict with federal requirements, for health or
safety reasons, or the building has been designated a historic site.
(9) Expanded Services. Expanded services are services
provided by the department that are outside the scope of OAR 330-130-0010
through 330-130-0100. Such services may include, but are not limited to:
(a) Acting as the owner’s agent on energy issues;
(b) Modeling during various phases of the design
process and when the building is occupied;
(c) Participating on design teams and providing
services for building projects following an alternate compliance path as
specified in OAR 330-130-0025;
(d) Building commissioning; and
(e) Providing resource conservation management
assistance and training as needed or requested by the agency.
Stat. Auth.: ORS 276.900 - 276.915
Stats. Implemented: ORS 469
Hist.: DOE 1-1990, f. & cert.
ef. 4-2-90; DOE 1-1998, f. & cert. ef. 3-26-98; DOE 4-2001, f. 11-5-01, cert. ef. 11-15-01; DOE 1-2003, f. & cert. ef. 1-10-03;
DOE 5-2011, f. & cert. ef. 6-27-11
330-130-0050
Procedures for Class 2 Buildings
(1) Role of the agency. The agency shall determine that
the design incorporates all required prescriptive ECMs or all reasonable
cost-effective ECMs. ECMs or ECM packages with a Simple Payback shorter than
equipment life shall be considered cost-effective for Class 2 Buildings.
(2) Role of the department. The department has accepted
the Oregon Reach Code as a prescriptive package of measures deemed to result in
the definition of a highly efficient facility for Class 2 Buildings. The
department shall also be available to the agency to advise or suggest potential
energy saving measures.
(3) Project Reporting. The agency shall provide the department
with the list of all measures or packages installed in the building.
Stat. Auth.: ORS 276.900 - 276.915
Stats. Implemented: ORS 469
Hist.: DOE 1-1990, f. & cert.
ef. 4-2-90; DOE 1-1998, f. & cert. ef. 3-26-98; DOE 4-2001, f. 11-5-01, cert. ef. 11-15-01; DOE 1-2003, f. & cert. ef. 1-10-03;
DOE 5-2008, f. 7-29-08, cert. ef. 8-1-08; DOE 5-2011,
f. & cert. ef. 6-27-11
330-130-0055
Procedure for Leased Buildings
The department, in consultation with the agencies,
shall establish guidelines for incorporating energy efficiency requirements
into lease agreements of 10 years or more to be phased in as current leases
expire or as agencies enter into new agreements.
Stat. Auth.: Ch. 26, OL 2008 HB
3612
Stats. Implemented: ORS 276.900 -
276.915
Hist.: DOE 5-2008, f. 7-29-08,
cert. ef. 8-1-08; DOE 5-2011, f. & cert. ef. 6-27-11
330-130-0060
Service Charges
Charges to the agency by the department for services
shall be as follows:
(1) Class 1 Buildings:
(a) The charges by the department to the agency will be
based on an hourly rate for the actual hours worked on the project. Hourly
rates charged by the department and invoiced to the agency will include salary,
other payroll expenses, the federally allowed indirect rate for the department,
staff travel expenses, other service or supply costs, and administrative costs.
Invoices may be submitted to the agency by the department monthly commencing
one month after notification. Invoices will provide the hours of service and
the hourly rate. The maximum charge shall be calculated at $0.002 for each
dollar of capital construction cost unless otherwise agreed to in writing by
the agency and the department.
(b) The department will invoice the agency for all
final charges within 60 days following the completion of its work as described
in these rules. To ensure the agency receives the final invoice prior to
closing their construction accounts, the department may invoice in advance for
final building inspections and post-occupancy energy use tracking.
(2) Class 2 Buildings. No charge unless the agency
chooses to enter into an interagency agreement with the department.
(3) Charges do not include design team or energy
analyst services. The agency must obtain these services directly. Charges
include all services provided by the department or their representative in
fulfilling the requirements described in these rules. Charges do not include
services such as described in section 330-130-0040(9) “Expanded Services”
provided by the department.
(4) The director may waive charges for special
circumstances including, but not limited to, demonstration or pilot projects.
(5) All charges are subject to review and adjustment by
the director of the department.
Stat. Auth.: ORS 276.900 - 276.915
Stats. Implemented: ORS 469
Hist.: DOE 1-1990, f. & cert.
ef. 4-2-90; DOE 1-1998, f. & cert. ef. 3-26-98; DOE 4-2001, f. 11-5-01, cert. ef. 11-15-01; DOE 1-2002, f. 5-8-02, cert. ef. 5-13-02; DOE 1-2003, f. & cert. ef. 1-10-03;
DOE 5-2008, f. 7-29-08, cert. ef. 8-1-08; DOE 5-2011,
f. & cert. ef. 6-27-11
330-130-0070
Department Administrative Procedures
(1) The department shall provide information and
administer the program to ensure the program is in accordance with these rules.
(2) Under special circumstances, the director may waive
certain requirements under these rules, provided the intent of the program as
described in statute is maintained.
(3) The department has developed guidelines, which
contain recommended procedures, instructions, and information relating to these
rules. The department shall solicit agency comments on the guidelines on a
biennial basis and revise the guidelines as appropriate.
(4) The department shall compile information about
agency participation and ECM implementation into a database. The department
shall make database information available to agencies and use the data in
evaluating agency compliance with the objectives of ORS 276.900 through ORS
276.915.
(5) The department, the Oregon Department of
Administrative Services and the Oregon University System shall jointly prepare
a biennial report to the legislature on January 1 of every odd-numbered year.
Stat. Auth.: ORS 276.900 - 276.915
Stats. Implemented: ORS 469
Hist.: DOE 1-1990, f. & cert. ef. 4-2-90;
DOE 1-1998, f. & cert. ef. 3-26-98; DOE 4-2001, f.
11-5-01, cert. ef. 11-15-01; DOE 5-2008, f. 7-29-08,
cert. ef. 8-1-08; DOE 5-2011, f. & cert. ef. 6-27-11
330-130-0080
Procedures for Monitoring the
Reduction in Energy Use by State Agencies
In order to review whether an agency meets the
requirement to reduce the amount of use of energy by at least 20 percent from
the amount used by the agency in the 2000 calendar year or the first 12 month
period for which reliable energy use data exists, the following rules for
tracking energy use apply.
(1) Energy use shall be tracked on a monthly basis
using billing data. Electricity and heating fuels shall be tracked separately.
The use of standard commercially available software for uniform tracking is
recommended.
(2) Agencies must report and enter energy use on an
annual basis into the State Energy Use Database http://saeuc.wesd.org.
(3) Energy use per square foot of conditioned space
shall be tracked, where applicable. Where square footage is not applicable,
another metric by which to compare annual energy use must be used in
consultation with the Department.
(4) Weather adjustments relative to the base year 2000
are allowed if:
(a) The adjustments follow a standard process developed
by the department through the SEED Program Guidelines; and
(b) Both the raw and revised usage is reported.
(5) When significant changes of facility size or use
takes place, adjustments to the baseline energy consumption may be made.
(6) It is recommended that sub-metering of buildings
and/or major energy consuming equipment is added where advisable and feasible
in order to get better data on energy use and facilitate better energy
management of the facilities.
(7) To assure that the 20 percent energy use reduction
by 2015 goal is met, interim energy reduction goals shall apply:
(a) 10 percent reduction in energy use by the agency by
December 31, 2010; and
(b) 15 percent reduction in energy use by the agency by
December 31, 2012.
(8) If an agency fails to achieve and maintain the required
percent reduction by the dates in (7)(a) and (7)(b), the following rules apply:
(a) The agency must notify the department that it
failed to achieve or maintain the required percent energy savings by June 30th
of each subsequent year.
(b) Within 90 days of such notification, the agency
must submit to the department a corrective plan to reduce energy use by the
required percent. The plan must:
(A) Outline all modifications, procedures, and changes
that need to be introduced until the target is met and maintained; and
(B) The plan shall be in a format described in the SEED
Program Guidelines.
(c) The agency may request the department to provide
technical assistance in developing this corrective plan. In the event that the
agency requests assistance, the agency must compensate the department’s costs
for assistance in preparation or review of the plan.
(d) The agency must implement the corrective plan
within six months from the date of approval by the department. The agency shall
monitor progress, report to the department, and modify the plan as necessary
every six months, until the target reduction is achieved.
(e) This conservation plan and the results of remedial
action(s) must be included in the biennial report to the legislature, to be
jointly prepared by the department, the Oregon Department of Administrative
Services and the Oregon University System.
Stat. Auth.: ORS 276.900 - 276.915
Stats. Implemented: ORS 469
Hist.: DOE 4-2001, f. 11-5-01,
cert. ef. 11-15-01; DOE 1-2003, f. & cert. ef. 1-10-03; DOE 5-2008, f. 7-29-08, cert. ef. 8-1-08; DOE 5-2011, f. & cert. ef. 6-27-11
330-130-0090
Pre-qualification for persons
performing Energy Analysis and Energy Savings Performance Contracting Services
(1) The department shall establish criteria to prequalify
persons or firms to execute the provisions of this bill. Agencies must only
select persons or firms that have been prequalified by the department to
perform energy analysis and energy savings performance contracting services.
(2) Agencies that wish to hire a person or firm that
has not been previously prequalified by the department must request approval
from the department for exemption from this requirement. Only licensed
professional architects and engineers are considered eligible for exemption from
prequalification.
(a) Energy analyst
(A) The department shall establish a list of
pre-qualified energy analysts through an open RFP process that uses
qualifications-based scoring criteria to determine a person’s ability to
perform building energy analysis.
(B) An agency may hire an energy analyst not on the
approved list provided the energy analyst is a licensed engineer or architect
and meets the qualifications of the energy analyst described in the SEED
Program Guidelines. All energy analysis reports must be
stamped by a licensed engineer or architect.
(b) ESCO
(A) A qualifying firm will have demonstrated expertise
in the following areas:
(i) A prior record of successfully performing ESPCs on
projects involving existing buildings and structures that are comparable to the
project under consideration by the contracting agency; and
(ii) The financial strength to effectively guarantee
energy savings and performance under the ESPC for the project in question, or
the ability to secure necessary financial measures to effectively guarantee
energy savings under an ESPC for that project.
(B) Pre-qualification process: The department must
utilize a Request for Qualifications (RFQ) process as the first step in a
two-part process to pre-qualify energy service companies to perform energy
savings performance contracting services.
(C) RFQ proposal evaluation process: For ESPC proposal
evaluations, the department shall establish qualifications-based evaluation
factors that outweigh price-related factors, due to the fact that the RFQ
process is the first step of a two-step process used to establish a list of
pre-qualified firms that a contracting agency must choose from for distribution
of RFPs.
(3) Agencies must adhere to the following requirements
for ESPC projects:
(a) Only select persons or firms that have been
pre-qualified by the department to provide energy savings performance
contracting services.
(b) The agency must use the department’s template
contract documents for all phases of the ESPC contract.
(c) Only utilize ESPC for comprehensive facility
retrofits that include energy efficiency projects for two or more energy using
systems. These systems must contribute to at least 50 percent of a facility’s
total energy use.
(d) Only use ESPC for projects that save energy and
water resources.
(e) Only use ESPC for existing buildings that are two
or more years old.
(f) Limit eligible contracting phases to:
(A) Phase I parts A and B for the technical energy
audit and project development plan;
(B) Phase II Design Build contract; and
(C) Phase III for the energy savings guarantee and
measurement and verification contract.
(g) Not combine service agreements with an ESPC
contract. All service agreement contracts must be mutually exclusive.
(h) Advertise a simplified RFP as the second step of a
two-step process for final selection of an ESCO for ESPC services.
(i) Only distribute RFPs to ESCOs that have been
pre-qualified by the department.
(j) At a minimum, the RFP must include a technical
facility profile, mandatory pre-proposal walk-through, and an interview
process.
(k) Select qualifications-based evaluation factors that
outweigh price factors.
(l) Contract with a third party for commissioning and
measurement and verification services.
(m) Select a pre-qualified ESCO for third party
commissioning or measurement and verification services associated with the ESPC
project.
Stat. Auth.: Ch. 26, OL 2008 HB
3612
Stats. Implemented: ORS 276.900 -
276.915
Hist.: DOE 5-2008, f. 7-29-08,
cert. ef. 8-1-08; DOE 5-2011, f. & cert. ef. 6-27-11
330-130-0100
Pre-qualification for persons
performing Energy Commissioning, Auditing, and Performance Verification
Services
(1) The department shall establish criteria to
pre-qualify persons or firms to execute the provisions of this bill. Agencies
may select persons or firms that have been pre-qualified by the department to
perform auditing, commissioning, and performance verification services for
energy systems.
(2) Energy Auditor:
(a) The department shall maintain a list of
pre-qualified energy auditing firms. This list must be established through an
open RFP process using a qualification-based scoring criteria to determine a person’s or firm’s ability to perform energy audits in existing
buildings.
(b) A qualifying firm must demonstrate expertise in the
following areas:
(A) Commercial and industrial technology;
(B) Energy auditing equipment, heating, ventilating,
and air conditioning systems;
(C) Lighting design;
(D) Energy efficiency technology; and:
(E) Preventative maintenance procedures.
(c) Agencies may use the department’s list of
pre-qualified energy auditors for the selection of a person or firm to perform
energy conservation measure analysis of existing buildings.
(3) Commissioning Agent
(a) The department maintains a list of pre-qualified
commissioning firms. This list will be established through an open RFP process
that uses a qualifications-based scoring criteria to
determine a person’s or firm’s ability to perform commissioning of energy using
systems in new and existing buildings.
(b) At least one individual employed by the firm must
be a member of a building commissioning professional association such as
Building Commissioning Association (BCA), National Environmental Balancing
Bureau (NEBB), or Associated Air Balance Council (AABC).
(c) Agencies may use the department’s list of
pre-qualified commissioning agents for the selection of a person or firm to
perform commissioning services for energy efficiency projects in new and
existing buildings.
(4) Measurement and verification.
(5) Agencies may select from the list of pre-qualified
ESCOs described in OAR 330-130-0090(2)(b) or the list of commissioning agents
described in OAR 330-130-0100(3) for the measurement and verification of
implemented energy efficiency measures.
Stat. Auth.: Ch. 26, OL 2008 HB
3612
Stats. Implemented: ORS 276.900 -
276.915
Hist.: DOE 5-2008, f. 7-29-08,
cert. ef. 8-1-08; DOE 5-2011, f. & cert. ef. 6-27-11
Notes
1.) This online version of the OREGON BULLETIN is provided for convenience of reference and enhanced access. The official, record copy of this publication is contained in the original Administrative Orders and Rulemaking Notices filed with the Secretary of State, Archives Division. Discrepancies, if any, are satisfied in favor of the original versions. Use the OAR Revision Cumulative Index found in the Oregon Bulletin to access a numerical list of rulemaking actions after November 15, 2010.
2.) Copyright 2011 Oregon Secretary of State: Terms and Conditions of Use |